Product Specification Text

 Damper Control Systems

Safegard V4 Intelligent Damper Control & Monitoring System

  • 300°C for 120mins and 600°C 30mins damper interface applications (HDIE) - 3rd party witnessed
  • 300°C for 120mins and 600°C 30mins damper actuator applications (HDAE) - 3rd party witnessed
  • All system wide activity logged and viewable for diagnostics and maintenance
  • Allows for phased commissioning and future expansion
  • Ethernet/IP compliant
  • Flexibility to accommodate any last minute changes to strategy, zones, damper quantities, references and descriptions etc.
  • Full Boolean logic to accommodate complex I/O cause & effect
  • Full configuration and diagnostics from Panel PC
  • Graphical user interface (GUI) displays live damper status (open, closed, travelling or fault) and all damper details, including specific location, as well as cause and effect strategies
  • Cause and effect scenarios easily accommodated
  • CE marked, LVD and EMC compliant
  • Completely flexible to meet practically any building’s damper requirements
  • Damper interfaces accept up to 2 off local heat/smoke detectors for cause & effect programming, except for 3P
  • Damper interfaces available in 24V, 120V or 230V, except for 3P (24V)
  • Damper interfaces provide local indication of open, closed, travelling or fault
  • Damper interfaces in purpose built IP54 enclosures for smoke fire dampers, smoke dampers, fire dampers, balanced smoke extract or modulating dampers
  • EMC Tested to EN61326-1: 2006 +Corr1 +Corr2
  • LVD Tested to EN61010-1: 2010 + Corr1:2011
  • Meets the EN harmonized standard for railway environments EN50121-4:2006 and London underground
  • Multiple options for monitoring dampers, individually or by group or zone - output contacts can be triggered when a predefined percentage within a group or zone change position
  • Multiple wiring configurations to include radial or loop topology
  • Open (nonproprietary) & interoperable protocol (LonWorks® and/or Modbus) allows support by others and future proof lifecycle maintenance costs
  • Optional conventional or touch screen fireman’s override panels
  • Optional e mail and text out facility
  • Optional full remote access via internet
  • Optional mimic panels
  • Optional networking of panels with control and monitoring from any panel - up to 16 off networked panels
  • Panel PC driven system with real-time graphic displays
  • Panel PC utilises solid state technology and solid state drive for optimum reliability
  • Powerful and flexible functionality enables standardisation of software (no bespoke site specific versions required)
  • RS-232, Modbus (RS-485) or BACnet over IP optional BMS links provided enabling connection from Safegard V4 to a BMS to read damper positions, I/O etc.
  • System designed to cater for environmental occupancy (energy saving) as well as the building’s smoke/fire strategy.
  • System provides full report of all “as installed” devices and cause & effect programming
  • Text fields facilitate clear description of all I/O devices at GUI
  • Three levels of alarm priority
  • Unique automatic scheduled damper testing initiated by user, an input or a scheduled task, including omit option for critical dampers. Separate test log provided.
  • Up to 512 off I/O per panel
  • Up to 64 off networks per panel

     

    Safegard EMB Smoke/Fire Damper Control & Monitoring System

    Safegard Electro-mechanical panel based system providing control and continuous monitoring of smoke/fire dampers. The Safegard EMB system is a purposely manufactured panel to meet specific customer requirements for zone operation and continuous monitoring of smoke/fire dampers. Each panel shall be designed to suit project requirements. Each damper to have individual indication to provide open and closed status via the damper motor auxiliary switches. Zonal control provided via a keyswitch operation or a fire alarm input.

     

     

    Smoke & Fire

    Generic Damper Statement

    Actionair & Safegard dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Actionair - Smoke/Shield PTC™ Fail-Safe Closed Operation

    Actionair smoke/fire dampers c/w unique proportional torque control snaplock actuators and prewired dual failsafe fusible links. Smoke/fire dampers having galvanised spigotted casing and St/St blades & side seals. Blades incorporate a synthetic seal to ensure low closed blade leakage and are fully compliant with the latest International, European & BS standards (ISO10294-1, EN1366-2 & BS ISO 10294-1) & the old BS standard BS476 part 20. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s. Each damper to be fitted with expansion/installation Hevac frame or stud wall expansion/installation frame c/w cleats where required on damper schedule.

    Actionair Smoke/Shield utilises Mode 5/6 Belimo BF-T based fire safety actuators having unique proportional torque control, snaplock connection and guaranteed elevated temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system. Each actuator has a dual failsafe pre-wired electro thermal fusible link rated at 72°C for internal & external duct temperature sensing and is complete with a manual external actuator test switch.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Rf-t manual Fire Damper and motorised Fire Damper (Smoke/Fire Damper) – Fire tested to class EIS – CU-LT & CU2

     These dampers are available 200 x 100 – 1500 x 1000mm. Also, the CU2 is available fire tested in a multiple arrangement in a solid wall.

    Actionair – Circular Smoke/Shield Fail-Safe Closed Operation – Fire tested to class ES

     Actionair circular smoke/fire dampers c/w complete with two installation flanges for easy fitting into stud and solid wall applications. Circular smoke/fire dampers having galvanised spigotted casing and St/St blade. Blade incorporates a synthetic seal to ensure low closed blade leakage. Fully compliant with the latest International, European & BS fire test standards (ISO10294-1, EN1366-2 & BS ISO 10294-1) class ES and are CE marked where possible to EN15650. Complies with Class A, B & C of DW144 and should be installed to comply with DW145. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s. Available in standard duct sizes 100mm to 355mm diameter. 

     The CSS Damper utilises a Compact Control Mode (Mode 5 –24V or Mode 6 – 230V) based on the Belimo BLF-T based fire safety actuators having guaranteed elevated temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system. Each actuator has a dual failsafe pre-wired electro thermal fusible link rated at 72°C for internal & external duct temperature sensing and is complete with a manual external actuator test switch.

     Actionair dampers are CE marked where possible and LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Rf-t manual Fire Damper and motorised Fire Damper (Smoke/Fire Damper) – Fire tested to class EIS – CR120

     Optimised circular fire damper with thin insulated blade, fusible link aligned with the blade, and the transmission located outside the tunnel all contributing to minimum pressure loss. The damper is available in sizes from 100mm to 315mm. Its galvanized steel tunnel contributes to the light weight of the damper.

    Actionair- Vent/Shield PTC™ Fail-Safe Open Operation

    Actionair smoke release dampers c/w unique proportional torque control snaplock actuators and prewired dual failsafe fusible links. Smoke release dampers having galvanised spigotted casing and St/St blades & side seals. Blades incorporate a synthetic seal to ensure low closed blade leakage and when closed are fully compliant with the latest International, European & BS standards (ISO10294-1, EN1366-2 & BS ISO 10294-1) & the old BS standard BS476 part 20. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s. Each damper to be fitted with expansion/installation Hevac frame or stud wall expansion/installation frame c/w cleats where required on damper schedule.

    Actionair Vent/Shield utilises Mode 5/6 Belimo BF-T based fire safety actuators having unique proportional torque control, snaplock connection and guaranteed elevated temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system. Each actuator has a dual failsafe pre-wired electro thermal fusible link rated at 72°C for internal & external duct temperature sensing and is complete with a manual external actuator test switch.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Actionair – Circular Vent/Shield Fail-Safe Open Operation – Fire tested to class ES in closed blade position

    Actionair circular smoke/fire dampers c/w complete with two installation flanges for easy fitting into stud and solid wall applications. Circular smoke/fire dampers having galvanised spigotted casing and St/St blade. Blade incorporates a synthetic seal to ensure low closed blade leakage. Fully compliant with the latest International, European & BS fire test standards (ISO10294-1, EN1366-2 & BS ISO 10294-1) class ES in the closed blade position and are CE marked where possible to EN15650. Complies with Class A, B & C of DW144 and should be installed to comply with DW145. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s. Available in standard duct sizes 100mm to 355mm diameter. 

    The CSS Damper utilises a Compact Control Mode (Mode 5 –24V or Mode 6 – 230V) based on the Belimo BLF-T based fire safety actuators having guaranteed elevated temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system. Each actuator has a dual failsafe pre-wired electro thermal fusible link rated at 72°C for internal & external duct temperature sensing and is complete with a manual external actuator test switch.

    Actionair dampers are CE marked where possible and LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Actionair  - Hot/Shield PTC™       Fail-Safe Closed Operation

    High Operating Temperature Smoke Damper (300°C for 1 hour)

    Actionair smoke dampers c/w thermally enclosed unique proportional torque control snaplock actuators. Smoke dampers having galvanised spigotted casing and St/St blades & side seals. Blades incorporate a synthetic seal to ensure low closed blade leakage and are fully compliant, when closed, with BS476 part 20. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s.

    Actionair Hot/Shield utilises Mode HM5/6 thermally enclosed Belimo BF -T based fire safety actuators having unique proportional torque control, snaplock connection and guaranteed 300°C for 1 hour temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Actionair  - Hot/Shield Vent PTC™ Fail-Safe Open Operation

    High Operating Temperature Smoke Damper (300°C for 1 hour)

    Actionair smoke release dampers c/w thermally enclosed unique proportional torque control snaplock actuators. Smoke release dampers having galvanised spigotted casing and St/St blades & side seals. Blades incorporate a synthetic seal to ensure low closed blade leakage and are fully compliant, when closed, with BS476 part 20. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s.

    Actionair Hot/Shield Vent utilises Mode HVM5/6 thermally enclosed Belimo BF -T based fire safety actuators having unique proportional torque control, snaplock connection and guaranteed 300°C for 1 hour temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Safegard Smoke/Fire Dampers – Safegard SFD-EN

    Safegard SFD-EN series, having galvanised spigotted casing and st/st aerodynamic interlocking blades incorporating synthetic seal with steel blade end bearings and peripheral gasketting. Fully compliant with the latest International, European & BS standards (ISO10294-1, EN1366-2 & BS ISO 10294-1) & the old BS standard BS476 part 20. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 15m/s. Each damper to be fitted with expansion/installation Hevac frame or stud wall expansion/installation frame where required on damper schedule.

    Safegard smoke/fire dampers utilise  Belimo BF-T based fire safety series actuators and the actuator / damper connection is by means of "Snaplock" drive interface mechanism to ensure positive control and guaranteed elevated temperature operation. Each actuator has two built in, non adjustable, auxiliary switches for connection to a Safegard smoke/fire damper control & monitoring system. Each actuator has a dual failsafe pre-wired electro thermal fusible link rated at 72°C for internal & external duct temperature sensing and is complete with a manual external actuator test switch.

    Safegard dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

     

     

    Fire

    Fire Dampers (FD’s) - Fire/Shield– Fire tested to class E

    Actionair Fire/Shield 101 series, having galvanised spigotted casing, St/St blades partially within the airstream & St/St side seals. Each damper has unique self latching fusible link mechanism rated at 72°C. Compliant with BS476 Part 20 and Class A, B & C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 20m/s.  Each damper to be fitted with expansion/installation Hevac frame or stud wall expansion/installation frame c/w cleats where required on damper schedule. For St/St blades out of the airstream on dampers > 250mm in height, specify Actionair Fire/Shield 201 series.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    FD’s are designed for applications in normal dry filtered air systems and should be tested at least annually. FD’s situated in dust laden and similar atmospheres should be tested more frequently, all in accordance with BS9999 Test Frequency.

    Due to the fact that these dampers have to be physically released and reset, particular attention should be paid to access which should be available from both sides of the FD. Also, it is very awkward to reset dampers when they are less than 200mm Sq or Circ and therefore automatic Smoke Fire Dampers (SFD’s) should be fitted.

    It should be noted that Safegard Systems always recommends the use of SFD’s as FD’s do not prevent the spread of smoke and they are impractical to regularly test.

    Fire Dampers (FD’s) - FB

    Actionair FBL series, having galvanised spigotted casing and galvanised blades partially within the airstream. Each damper has a chain bar type fusible link mechanism rated at 72°C. Compliant with BS476 Part 20 and Class A, B & C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 20m/s.  Each damper to be fitted with expansion/installation Hevac frame or stud wall expansion/installation frame c/w cleats where required on damper schedule. For blades out of the airstream on dampers > 250mm in height, specify Actionair FBH series.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    FD’s are designed for applications in normal dry filtered air systems and should be tested at least annually. FD’s situated in dust laden and similar atmospheres should be tested more frequently, all in accordance with BS9999 Test Frequency.

    Due to the fact that these dampers have to be physically released and reset, particular attention should be paid to access which should be available from both sides of the FD. Also, it is very awkward to reset dampers when they are less than 200mm Sq or Circ and therefore automatic Smoke Fire Dampers (SFD’s) should be fitted.

    It should be noted that Safegard Systems always recommends the use of SFD’s as FD’s do not prevent the spread of smoke and they are impractical to regularly test.

    Door Dampers – Trans/Shield

    Actionair Trans/Shield stainless steel sliding palte dampers are designed for air transfer through fire rated doors and dry wall partitions providing up to 2 hour fire protection. Available in 5 off nominal sizes c/w manual or electrical release. Compliant with BS476 Part 20.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Fire Dampers (FD’s) – Safegard FDA

    Safegard FD series, having galvanised spigotted casing and galvanised blades partially within the airstream. Each damper has a straight bar fusible link rated at 72°C. Compliant with BS476 Part 20 and Class A, B & C of DW144. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 12.5m/s.  Each damper to be fitted with expansion/installation Hevac frame or stud wall angle frame where required on damper schedule. For blades out of the airstream specify FDB.

    FD’s are designed for applications in normal dry filtered air systems and should be tested at least annually. FD’s situated in dust laden and similar atmospheres should be tested more frequently, all in accordance with BS9999 Test Frequency.

    Due to the fact that these dampers have to be physically released and reset, particular attention should be paid to access which should be available from both sides of the FD. Also, it is very awkward to reset dampers when they are less than 200mm Sq or Circ and therefore automatic Smoke Fire Dampers (SFD’s) should be fitted.

    It should be noted that Safegard Systems always recommends the use of SFD’s as FD’s do not prevent the spread of smoke and they are impractical to regularly test.

     

     

     

    Air

    Volume Control Dampers – Air/Shield series Aerofoil

    Actionair Air/Shield series aerofoil, having galvanised steel flanged casing and stainless steel aerofoil opposed blades. Each damper has a manual push and turn knob with locking mechanism. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 12m/s.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Volume Control Dampers – Air/Shield series Aeroseal

    Actionair Air/Shield series aeroseal, having galvanised steel flanged casing and stainless steel aerofoil opposed blades c/w synthetic seal and stainless steel side seals. Each damper has a manual quadrant with locking mechanism. Complies with Class A, B & C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 12m/s.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Actionair Series Circulair/Balance Dampers

    Circulair/balance dampers comprise of a single 1.2 galvanised steel blade and 0.7 mm galvanized steel case complete with manual quadrant control. Casing leakage conforms to DW144 Class C up to 1000Pa.

    Volume Control Dampers (AHU) - Energy/Shield 35

    Actionair Energy/Shield 35 series, having galvanised steel flanged casing and galvanised steel triple-vee opposed blades. Manual or motorised options available. Complies with Class  C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 10m/s.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Volume Control Dampers c/w Blade Seal (AHU) - Energy/Shield 36

    Actionair Energy/Shield 36 series, having galvanised steel flanged casing, galvanised steel triple-vee opposed blades c/w synthetic seal and stainless steel side seals. Manual or motorised options available. Complies with Class C of DW144. Operating total system pressure ≤ 1000 Pascals and duct velocities ≤ 10m/s.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained.

    Volume Control Dampers c/w Blade Seals and Bearings - Energy/Shield 50

    Actionair Energy/Shield 50 series, having galvanised steel flanged casing and aerodynamic aluminium aerofoil opposed blades c/w synthetic blade seals and bearings. Manual or motorised options available. Complies with Class C of DW144 and EN1751 class 3. Operating total system pressure ≤ 1500 Pascals and duct velocities ≤ 20m/s.

    Actionair dampers are LPCB approved (Loss Prevention Certification Board) meaning 3rd party regular re-assessment/audit testing to ensure quality of product & service are maintained

 